Thermal Differential Smoke Detector BSR-6060/A for BSR-21/1116 921606002
The BSR-6060 / A is a thermal and thermal differential detector at the same time. Works with panels BSR-2104 and BSR-2114. It sends a proportional value to the table that depends on the room temperature and its growth rate.
This value is 100 at a temperature of 56 degrees Celsius, and increases by one unit for each degree that the temperature rises. If the temperature rises sharply (at a rate of more than 5 degrees per minute) the value sent by the detector to the panel is 127. The proportional setting of the value 100 is approved in accordance with EN 54-5: 2000 + A1: 2002.
The smoke detector consists of two parts. A plastic base mounted on the roof and the main body of the detector that fastens to the plastic base with a simple rotation to the right. The detectors have an indicator light that lights up continuously in case of fire detection, until a cancellation command is given by the panel.
It also stays on when the sirens are stopped by the panel to indicate the detector from which the alarm was given. Turns off only after resetting the panel. The LED indicator also flashes every 8 sec as an indicator of good operation.